FUEL/EMISSIONS STRATEGY
EPA Certied for Stationary
Emergency Application
(EPA Tier 3 emissions levels)
FULL RANGE OF ATTACHMENTS
Wide range of bolt-on system expansion
attachments, factory designed and tested
Flexible packaging options for easy and cost
effective installation
SINGLE-SOURCE SUPPLIER
Fully prototype tested with certied torsional
vibration analysis available
WORLDWIDE PRODUCT SUPPORT
Cat dealers provide extensive post sale support
including maintenance and repair agreements
Cat dealers have over 1,800 dealer branch stores
operating in 200 countries
The Cat S•O•S
SM
program cost effectively detects
internal engine component condition, even the
presence of unwanted uids and combustion
by-products
Cat
®
Model D50-6S, Single Phase
CAT C4.4 DIESEL ENGINE
Reliable, rugged, durable design
Field-proven in thousands of applications worldwide
Four-stroke diesel engine combines consistent
performance and excellent fuel economy with
minimum weight
• Electronic engine control
GENERATOR SET
Complete system designed and built at ISO 9001
certied facilities
Factory tested to design specications at full load
conditions
CAT EMCP 4 CONTROL PANELS
• Simple user friendly interface and navigation
Scalable system to meet a wide range ofcustomer
needs
Integrated Control System and Communications
Gateway
SEISMIC CERTIFICATION
• Seismic Certication available
Anchoring details are site specic, and are
dependent on many factors such as generator set
size, weight, and concrete strength.
IBC Certication requires that the anchoring system
used is reviewed and approved by a Professional
Engineer
Seismic Certication per Applicable Building codes:
IBC 2000, IBC 2003, IBC 2006, IBC 2009, IBC 2012
CBC 2007, CBC 2010
Pre-approved by OSHPD and carries an
OSP-0321-10 for use in healthcare projects in
California
STANDBY
50 ekW 50 kVA
PRIME
45 ekW 45 kVA
60 Hz 1800 rpm 240/120 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
DIESEL GENERATOR SET
Image shown may not
reect actual package.
FEATURES
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - 45 ekW 45 kVA

FUEL/EMISSIONS STRATEGY• EPA Certied for Stationary Emergency Application (EPA Tier 3 emissions levels)FULL RANGE OF ATTACHMENTS• Wide range of bo

Page 2 - PRIME 45 ekW 45 kVA

STANDBY 50 ekW 50 kVAPRIME 45 ekW 45 kVA60 Hz 1800 rpm 240/120 VoltsFACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT System Standard Optional A

Page 3

STANDBY 50 ekW 50 kVAPRIME 45 ekW 45 kVA60 Hz 1800 rpm 240/120 VoltsSPECIFICATIONSCAT EMCP 4 SERIES CONTROLSEMCP 4 controls including:– Run / Auto / S

Page 4

STANDBY 50 ekW 50 kVAPRIME 45 ekW 45 kVA60 Hz 1800 rpm 240/120 VoltsTECHNICAL DATAOpen Generator Set – 1800 rpm/60 Hz/480 Volts P3454A P3454BTier 3 ST

Page 5

STANDBY 50 ekW 50 kVAPRIME 45 ekW 45 kVA60 Hz 1800 rpm 240/120 VoltsRATING DEFINITIONS AND CONDITIONS5Applicable Codes and Standards: AS1359, CSA C22.

Page 6

STANDBY 50 ekW 50 kVAPRIME 45 ekW 45 kVA60 Hz 1800 rpm 240/120 VoltsDIMENSIONSPackage DimensionsLength1932 mm 76 inWidth1110 mm 44 inHeight 1767 mm 46